Data Center Solution High Efficiency Digital Modular Online UPS
Single Phase Rack Mounted Container Modular Data Center UPS
Modular UPS Double Conversion Online UPS with Static Switch
Main Features
· Double conversion topology technology, pure sine wave output.
· Advanced DSP digital control technology.
· Environmental Friendly and energy saving, as the input power factor is up to 0.99.
· Wide turn on voltage range , 110-300VAC ≤50% load, 176-300VAC ≤100% load
· 0ms Line-Bat transfer , ensure the safety and reliablity of load.
· ECO mode optional, reduce the UPS power consumption.
· Low audible noise (below 55 dB), will not affect your daily life.
Specfictations
Single Phase Rack Mounted Container Modular Data Center UPS
Modular UPS Double Conversion Online UPS with Static Switch
Main Features
· Double conversion topology technology, pure sine wave output.
· Advanced DSP digital control technology.
· Environmental Friendly and energy saving, as the input power factor is up to 0.99.
· Wide turn on voltage range , 110-300VAC ≤50% load, 176-300VAC ≤100% load
· 0ms Line-Bat transfer , ensure the safety and reliablity of load.
· ECO mode optional, reduce the UPS power consumption.
· Low audible noise (below 55 dB), will not affect your daily life.
Specfictations
Model | 1K | 2K | 3K | 6K | 10K | ||
Phase | Single phase with ground | ||||||
Input | |||||||
Rate capacity | 1KVA/800W | 2KVA/1.6KW | 3KVA/2.4KW | 6KVA/4.8KW | 10KVA/8KW | ||
Rate voltage | 110/115/120/127VAC or 220/230/240VAC | 220/230/240VAC | |||||
Turn on voltage range | 55-150VAC or 110-300VAC ≤50% load | 110-300VAC ≤50% load | |||||
85-140VAC or 160-280VAC ≤100% load | 176-300VAC ≤100% load | ||||||
Frequency range | 40~70Hz | 46~54Hz or 56~64Hz | |||||
Power factor | ≥0.99 100% load | ||||||
Output | |||||||
Rate voltage | 110/115/120/127VAC or 220/230/240VAC | 220/230/240VAC | |||||
Voltage regulation | ±1% | ||||||
Line mode frequency | 47~53Hz or 57~63Hz | 46~54Hz or 56~64Hz | |||||
Bat mode frequency | 50Hz or 60Hz | ||||||
Voltage harmonic | ≤3% R load | ≤3% R load | |||||
≤6% RCD load | ≤5% RCD load | ||||||
Crest ration | 3:01 | ||||||
Line-Bat transfer | 0ms | ||||||
INV-Bypass transfer | ≤4ms | 0ms | |||||
Over load | 105%±5%<load≤125%±5%:1min;125%±5%< load ≤150%±5%:30s;load>150%±5%:300ms; ( transfer to bypass and alarm) | ||||||
Efficiency | |||||||
Line mode | > 88% | > 88% | > 90% | > 92% | > 93% | ||
Bat mode | > 83% | > 85% | > 88% | > 90% | > 91% | ||
Bat | |||||||
Number | 2 | 4 | 6 | 16 or 20 | |||
Charger voltage | 27.4VDC | 54.7VDC | 82.1VDC | 218.4VDC/273VDC | |||
Charge current (stand) | 1A | 1A/2A | |||||
Charge current(long) | 1A/2A/4A/6A(adjustable,20Bat can't select 6A) | ||||||
Size(length*width*height)and weight | |||||||
Stand UPS(mm) | 282*145*220 | 397*145*220 | 421*190*318 | 369*190*688(6K 16 No.)/ | |||
442*190*688 | |||||||
Weight(kg) | 9.8 | 17 | 27.6 | 61 | 74 | 66 | 76 |
Long time UPS(mm) | 282*145*220 | 397*145*220 | 369*190*318 | 442*190*318 | |||
Weight(kg) | 4.1 | 6.8 | 7.4 | 12 | 16 | ||
Environment | |||||||
Work temperature | 0ºC~40ºC | ||||||
Work humidity | 20%~95% | ||||||
Audible noise | ≤50dB | ≤55dB | ≤58dB | ||||
Communication | RS-232/USB/SNMP card adjustable |